Why does retrieving the battery charge value from a Synology NAS DS413's APC Back-UPS work with iReasoning MIB Browser but fail with Paessler SNMP Tester and PRTG, showing a NAN (Unknown data type) error?
As of 05/08/2015 PRTG is able to natively recognize this datatype. PRTG's version 15.3.18.3378 is able to recognize the Opaque Float format, in that version a SNMP Custom Sensor for the 1.3.6.1.4.1.6574.4.3.1.1.0 OID displays the correct result 100.
More
Script for status, UPS load, estimated battery runtime and battery voltage.
Param( [string]$hostname, [string]$community ) #Get UPS status $var = cmd /c "C:\Program Files\usr\bin\snmpget.exe" -c $community -v 2c -Oqv $hostname .1.3.6.1.4.1.6574.4.2.1.0 $status = $var.replace(" ","") $upsstatus = switch -regex ($status) { "OBDISCHRG" {"3"; break} "OLCHRG" {"2"; break} "OL" {"1"} } #Get Battery Charge $var = cmd /c "C:\Program Files\usr\bin\snmpget.exe" -c $community -v 2c -Oqv $hostname .1.3.6.1.4.1.6574.4.3.1.1.0 $pos = $var.IndexOf(".") $leftPart = $var.Substring(0, $pos) #Get battery runtime $var = cmd /c "C:\Program Files\usr\bin\snmpget.exe" -c $community -v 2c -Oqv $hostname .1.3.6.1.4.1.6574.4.3.6.1.0 $time = $var/3600 #Get current load $var = cmd /c "C:\Program Files\usr\bin\snmpget.exe" -c $community -v 2c -Oqv $hostname .1.3.6.1.4.1.6574.4.2.12.1.0 $pos = $var.IndexOf(".") $load = $var.Substring(0, $pos) #Get battery voltage $var = cmd /c "C:\Program Files\usr\bin\snmpget.exe" -c $community -v 2c -Oqv $hostname .1.3.6.1.4.1.6574.4.3.2.1.0 $voltage = $var #Create Sensor Write-Host "<prtg>" Write-Host "<result>" Write-Host "<channel>UPS Status</channel>" Write-Host "<value>$upsstatus</value>" Write-Host "<valuelookup>prtg.standardlookups.Synology.UPSstatus</valuelookup>" Write-Host "</result>" Write-Host "<result>" Write-Host "<channel>Battery Charge Level</channel>" Write-Host "<value>$leftPart</value>" Write-Host "<unit>Percent</unit>" Write-Host "<LimitMinError>30</LimitMinError>" Write-Host "<LimitMinWarning>40</LimitMinWarning>" Write-Host "<LimitMode>1</LimitMode>" Write-Host "</result>" Write-Host "<result>" Write-Host "<channel>UPS load</channel>" Write-Host "<value>$load</value>" Write-Host "<unit>Percent</unit>" Write-Host "<LimitMaxError>95</LimitMaxError>" Write-Host "<LimitMaxWarning>90</LimitMaxWarning>" Write-Host "<LimitMode>1</LimitMode>" Write-Host "</result>" Write-Host "<result>" Write-Host "<channel>Battery Est. Runtime</channel>" Write-Host "<value>$time</value>" Write-Host "<unit>s</unit>" Write-Host "<float>1</float>" Write-Host "<LimitMinError>0.1</LimitMinError>" Write-Host "<LimitMinWarning>0.2</LimitMinWarning>" Write-Host "<LimitMode>1</LimitMode>" Write-Host "</result>" Write-Host "<result>" Write-Host "<channel>Battery Voltage</channel>" Write-Host "<value>$voltage</value>" Write-Host "<unit>V</unit>" Write-Host "<float>1</float>" Write-Host "<LimitMode>1</LimitMode>" Write-Host "</result>" Write-Host "</prtg>"
You need this lookup to show the status circle:
<?xml version="1.0" encoding="UTF-8"?> <ValueLookup id="prtg.standardlookups.Synology.UPSstatus" desiredValue="0" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="PaeValueLookup.xsd"> <Lookups> <SingleInt state="Ok" value="1">AC Power</SingleInt> <SingleInt state="Warning" value="2">AC Power / Battery charging</SingleInt> <SingleInt state="Error" value="3">Battery Power</SingleInt> </Lookups> </ValueLookup>
Edit: Added <valuelookup>prtg.standardlookups.Synology.UPSstatus</valuelookup> to the output of the first channel "UPS Status".