Dear, i have huawei 5720 switch and OID 1.3.6.1.4.1.2011.5.25.31.1.1.3.1.8 for measurement of optical power on a interface, but i dont know how to configure prtg sensor for monitoring optical power.

Thanks


Article Comments

Attention: This article is a record of a conversation with the Paessler support team. The information in this conversation is not updated to preserve the historical record. As a result, some of the information or recommendations in this conversation might be out of date.

Hi sanghera,

Thank you very much for your question.

The easiest approach is to deploy a SNMP Custom and enter the OID while the sensor creation.

According to this site it appears that the provided value is expanded 100 times.

hwEntityOpticalRxPower 1.3.6.1.4.1.2011.5.25.31.1.1.3.1.8
The receive power of the optical module. Unit: dBm. the value is expanded 100 times, so the real value should be reduced 100 times

The division of 100 can be configured in the Settings tab of the created sensor afterwards.

Best regards,
Sebastian