I have created a custom SNMP Sensor and its reporting wrong Values (see Table).

Correct ValuesSNMP TesterPRTG
93148979200931489792002960064512
327683276832768
2555505541122555505541122959998976
1544156200961544156200964086398976
93148946432931489464322147483648

I have recreated the sensor multible times. Restartet PRTG Host (Windows Server 2016) and Target Host(Debain 9). Why are all values wrong except the smalles one?


Article Comments

We're currently having a overflow bug within the SNMP Custom (Advanced) Sensor - is that the one you're using? If so, kindly check if a SNMP Custom Sensor reads the values correctly and use that one in the meantime.


Kind regards,
Stephan Linke, Tech Support Team


Mar, 2018 - Permalink

Yes Im using the SNMP Custom Advanced Sensor. I've vertified the last vew days that the SNMP Custom Sensor is not Affected!

Is there a Bugtracker?

Thank you!


Mar, 2018 - Permalink

We do have a bugtracker, but it's only for internal use. The issue is currently in the review process. Keep an eye on https://www.paessler.com/prtg/history/stable to see when it's fixed. As of right now, the SNMP Custom sensor is the only workaround.


Kind regards,
Stephan Linke, Tech Support Team