Hi

I uses switches with redundant power supply - the problem is when the redundant supply goes down and come back again the System Health Power Supplies Sensor stay's on error.(The switch don't reboot because the other power supply is working) Both power supply are o.k.(checked it on the cli) I have to reboot the switch and re-add the System Health Power Supplies Sensor to get the sensor o.k.

Have you any suggestions what i can do

Thanks Plane1


Article Comments

As far as I know this has to do with the fans of the PSU getting a new OID after a reboot, hence the power supply will error. As of right now, you might want to remove the lookup on that channel in it's options and use a SNMP custom sensor to monitor the OID 1.3.6.1.4.1.9.9.13.1.5.1.3.index

Use the same lookup file as the original sensor did. Now, after the reboot, you can change the OID accordingly. Use the SNMP Tester and do a walk on the OID to get the correct index value (and replace the index in the OID with it).

Sorry, that's all that we can do about it :(


May, 2015 - Permalink