I have an licensed PRTG-Server working in two different networks on the same network interface. I am trying to get informations about an older HP-UPS via SNMP v1.
The device is reachable via PING. The SNMP-community/port on the SNMP-Tester and the Server are completely the same. When I run a test with SNMP Tester I get all Informations I want. When I configure a sensor for this device, the SNMP gets an timeout "-2003".
Even when I try the "Read Device uptime"... SNMP Tester works PRTG Server itself doesnt work
Ping does work, and also other sensors like http e.g.
I can´t find the problem... there is no visible difference. Do you have any idea?
Article Comments
Thank you for your reply and advise. As I can see in Wireshark, the sensor from prtg-server is checking via snmp on the wrong network. (one network card, two different networks) In SNMP-Tester you can set your local IP and it works fine.
Is it possible to change that behavior in PRTG-Server?
Oct, 2021 - Permalink
Hello again,
I found the "problem" at the server itself. In the "PRTG Administration Tool", the probe settings for monitoring was only set for one IP adress. I've set the settings to automatic and now it works fine. Problem solved.
Thank you again! :)
Oct, 2021 - Permalink
Hi,
The error -2003 indicates a general connection problem with the target server. This means that the Core Server didn't receive a respond from the target device. You may check with Wireshark whether there is a difference between SNMP Tester and PRTG.
Kind regards
Felix Wiesneth - Team Tech Support