I want to utlilize the SNMP Custom Advanced Sensor to monitor the HA status of Fortigate units. The OID's are 1.3.6.1.4.1.12356.101.13.2.1.1.12.1 and 1.3.6.1.4.1.12356.101.13.2.1.1.12.2. The first one is the status of the primary and the second one is the status of the secondary. I can create the sensor and return values but I do not see how to alarm on the expected change: value from 1 to 0, 0 being HA not synchronized.

How do I alarm when Integer is 0?

NORMAL STATE (Walk) 8/13/2021 7:36:11 AM (1604 ms) : 1.3.6.1.4.1.12356.101.13.2.1.1.12.1 = "1" [ASN_INTEGER] 8/13/2021 7:36:11 AM (1714 ms) : 1.3.6.1.4.1.12356.101.13.2.1.1.12.2 = "1" [ASN_INTEGER]

ABNORMAL STATE (Walk) 8/13/2021 7:36:11 AM (1604 ms) : 1.3.6.1.4.1.12356.101.13.2.1.1.12.1 = "1" [ASN_INTEGER] 8/13/2021 7:36:11 AM (1714 ms) : 1.3.6.1.4.1.12356.101.13.2.1.1.12.2 = "0" [ASN_INTEGER]


Article Comments

Attention: This article is a record of a conversation with the Paessler support team. The information in this conversation is not updated to preserve the historical record. As a result, some of the information or recommendations in this conversation might be out of date.

Hello Drew,

Thank you for your message.

To trigger an alert when the values change, you can use limits in the corresponding channel. In this case, you can configure the option "Lower Warning Limit" or "Lower Error Limit" to 1 and then configure the notification trigger accordingly.

If you have questions, let me know.

Regards.


Aug, 2021 - Permalink