Hello. I'm hoping somebody might be able to help me with getting our APC Netbotz 200 environment sensor reporting in our PRTG installation.
I've already imported the MIB and saved it out as the oidlib file PRTG wants to see and can see the list of sensors in the SNMP Library but whatever option I use, I'm unable to get a temperature value back. It either shows a ping or a minus value. From my internet searches, it appears that others have been successful but I've not found enough detail for me to follow.
Any assistance would be gratefully received.
Thanks in advance
Richard
Article Comments
Quote from irrexpr.com:
Both the AP9340 and the NetBotz 200 use the following OIDs for the temperature and humidity, as well as naming:
1.3.6.1.4.1.318.1.1.10.4.2.3.1.3.0.1 - Sensor Name
1.3.6.1.4.1.318.1.1.10.4.2.3.1.4.0.1 - Sensor Location
1.3.6.1.4.1.318.1.1.10.4.2.3.1.5.0.1 - Temperature
1.3.6.1.4.1.318.1.1.10.4.2.3.1.6.0.1 - Humidity
Like before, if you increment the last digit you'll get the different ports (.1 is for port 1, .2 is port 2, .6 is port 6, etc).
You can use those OIDs in combination with our SNMP Custom (Advanced) sensor.
Let me know if it worked out! :)
Kind regards,
Stephan Linke, Tech Support Team
Nov, 2017 - Permalink
Amazing, thank you Stephen!
Dec, 2017 - Permalink
Is there any way to get fahrenheit tenths of degrees? I only see full digits.
Aug, 2020 - Permalink
What's the actual output of these OIDs with the SNMP Tester? If they're actually floats, you could set the value to float in the Sensor settings.
Aug, 2020 - Permalink
Quote from irrexpr.com:
You can use those OIDs in combination with our SNMP Custom (Advanced) sensor.
Let me know if it worked out! :)
Kind regards,
Stephan Linke, Tech Support Team
Nov, 2017 - Permalink