Hi,
we get a new SNMP-Adapter(CS121) in our AEG-USV Protect 3.33. Now is the question how can i import the information from this SNMP-Adapter to PRTG?
Did anyone try this before? Are there any code to use?
Article Comments
Attention: This article is a record of a conversation with the Paessler support team. The information in this conversation is not updated to preserve the historical record. As a result, some of the information or recommendations in this conversation might be out of date.
Hi Sven,
thanks for your answer. I solve my problem with a PRTG "snmpcustomsensor" an the OID.
It works with: OID: 1.3.6.1.2.1.33.1.2.3 - Remaining Minutes OID: .1.3.6.1.2.1.33.1.2.4.0 - Battery Capacity
Best regards, Max
Nov, 2016 - Permalink
Hello Max-bfm,
Thank you for your question.
I assume you are referring to the GENEREX USV-Adapter CS121
If this is correct, please download the related MIB-File RFC1628cs121.MIB and use our MIB-Importer to generate an OIDlib-file which should be saved under C:\Program Files (x86)\PRTG Network Monitor\snmplibs.
Once you have done this, you can monitor the target with the "SNMP Library Sensor"
Here's a KB-article that describes the setup of "SNMP Library Sensors" and there's also a video that shows how to.
Please let us know, if you have any further questions.
Kind regards, Sven
Nov, 2016 - Permalink